| Series (VPPE) | Proportional pressure regulator |
|---|---|
| Valve function (1) | Normally closed |
| Pneumatic connection (1/8) | Female thread G1/8 |
| Pressure regulation range (6) | 0.06 ... 6 bar |
| Setpoint input for individual valves (010) | 0 ... 10 V |
|---|---|
| Operator unit/interface (E1) | LED display, 7-segment |
| Mounting (T) | Common supply manifold mounting (mounting rail) |
| Special material properties | None |
| Material housing | Anodised wrought aluminium alloy | ||
| Pneumatic connection, port 3 | G1/8 | ||
| Pneumatic connection, port 1 | G1/8 | ||
| Electrical connection | 5-pin M12 Plugs | ||
| Total accuracy | 1.25%FS | ||
| Hysteresis | 0,5 %FS | ||
| Product weight | 390 g | ||
| Degree of protection | IP65 | ||
| LABS (PWIS) conformity | VDMA24364-B2-L | ||
| Certificate issuing authority | UL E322346 | ||
| CE mark (see declaration of conformity) | To EU EMC Directive In accordance with EU RoHS Directive | ||
| Approval | RCM trademark c UL us listed (OL) | ||
| Operating medium | Compressed air to ISO 8573-1:2010 [7:4:4] Inert gases | ||
| Signal range analogue output | 0 - 10 V | ||
| Residual ripple | 10 % | ||
| Duty cycle | 100% | ||
| Operational voltage range DC | 21,6 V ... 26,4 V | ||
| Max. pressure hysteresis | 0,435 psi | ||
| Pressure regulation range | 0,06 bar ... 6 bar | ||
| Valve function | 3-way proportional pressure regulator | ||
| Type of reset | Mechanical spring | ||
| Symbol | 00995303 | ||
| Short circuit current rating | For all electrical connections | ||
| Mounting position | optional Preferably vertical | ||
| Type of actuation | Electric | ||
| Nominal size, supply | 5 mm |
| Note on materials | RoHS-compliant | ||
| Pneumatic connection, port 2 | G1/8 | ||
| Type of mounting | With through-hole | ||
| Temperature cooefficient | 0,04 %/K | ||
| Reproducibility | 0,5 %FS | ||
| Linearity | 1 %FS | ||
| Ambient temperature | 0 °C ... 60 °C | ||
| Media temperature | 10 °C ... 50 °C | ||
| Corrosion resistance class CRC | 2 - Moderate corrosion stress | ||
| CE marking (see declaration of conformity) | To UK instructions for EMC To UK RoHS instructions | ||
| KC mark | KC-EMV | ||
| Note on operating and pilot medium | Lubricated operation not possible | ||
| Signal range analogue input | 0 - 10 V | ||
| Switching output | PNP | ||
| Max. electrical power consumption | 4,2 W | ||
| Max. current consumption | 160 mA | ||
| Standard nominal flow rate | 800 l/min | ||
| Inlet pressure 1 | 0,6 MPa ... 0,8 MPa | ||
| Display type | LED indicator 3-digit | ||
| Type of piloting | Pilot actuated | ||
| Reverse polarity protection | For all electrical connections | ||
| Safety instructions | Safety position VPPE: if the power supply cable is interrupted, output pressure is maintained unregulated. | ||
| Design | Piloted diaphragm regulator | ||
| Sealing principle | Soft | ||
| Nominal size, exhaust | 2,5 mm |